North American low-voltage switchgear
There are two main types of low-voltage switchgear in North America. One is power switchgear, with the standard IEEE C37.20.1/UL1558, which belongs to primary distribution cabinets. The other is UL891 low-voltage distribution panel, which is a switchgear used on the user side.
The low-voltage distribution panel SWITCHBOARD reference standard UL891 has different types of access, such as front entry and rear entry. The DEAD FRONT COVER is fixedly installed in the form of a front cover plate, with a frame circuit breaker as the incoming line isolation and a molded case circuit breaker as the outgoing line. It can be a fixed or quick plug structure. The incoming cable can be connected in front of the cabinet or behind the cabinet, and the plastic shell outgoing cable can be connected on the front side.
Distribution panel standard:
■ ANSI C37.13, C37.16, C37.17,ANSI C37.50; ANSI/NEMA PB 2
■UL-891, CUL C22.2
The low-voltage side of transformers in North American projects generally uses Switcboard distribution panels, with the standard term Dead front Switcboard, which means that the front panel of the distribution panel is fixed and sealed, leaving only circuit breaker operation holes, such as the panel of the frame circuit breaker and the operating handle for moving and opening the molded case circuit breaker up and down. The frame circuit breaker can be manually or electrically operated, while the molded case circuit breaker can be manually opened and closed.
The maximum current of the distribution panel can reach 6000A, and the short-circuit breaking of the switch can reach 100kA. Unlike the switchgear, the installation density of the distribution panel is high, simple and efficient. The distribution panel does not require excessive protection level, internal arc level, short-term withstand current, compartment separation between functional units, excessive secondary control protection, complex operating mechanism, or rocking in and out. This structure ensures temperature rise under high installation density, facilitates and simplifies cable connections, simplifies maintenance operations, and greatly improves reliability.
The North American standard UL891 distribution panel has its unique design requirements, and the standard clearly defines the structural requirements. The horizontal busbar is located in the middle of the rear of the cabinet, generally in two groups, with a maximum current of 6000A and 150kA.
Especially for the outgoing lines of molded case circuit breakers, they must be installed horizontally and arranged in groups of Group Type. The quantity and capacity of the outgoing lines on both sides or one side are defined.
The current specification of the vertical busbar of the molded case circuit breaker output cabinet should adopt a dispersion factor according to the number of installed circuits, and also consider the current requirements for the expansion of the empty module space. According to the design, 16 250A molded case circuit breakers can be installed for output. If only 8 250A molded case circuit breakers are installed, the dispersion factor of the 8 molded cases may be 0.6, and the total current is 250 * 8 * 0.6=1200A. However, since only 8 modules are installed and there are still 8 empty molded case modules, according to the standard, a coefficient of 1.6 needs to be reserved, so the vertical busbar needs 1200 * 1.6=1920A.
The output current of UL891 molded case circuit breaker can reach 1200A, and one distribution panel can install four 1200A molded case circuit breakers as output circuits.
The UL891 distribution panel generally uses copper bars to directly fix the vertical busbar and the incoming end of the molded case circuit breaker. The outgoing side of the molded case circuit breaker is equipped with cable ends, that is, the stripped copper core of the cable can be directly inserted into the outgoing cable end of the molded case circuit breaker for connection. For high current, each phase can connect 4 300 square cables.
For incoming cabinets and bus tie cabinets, fixed frame circuit breakers are generally used. DEAD FRONT means that the front is completely fixed and generally not allowed to be opened, so using withdrawable circuit breakers is also meaningless.
The incoming cabinet is directly connected to the transformer box and reaches the horizontal busbar through the incoming circuit breaker. The outgoing line of the frame circuit breaker is connected by cables or connected to the load center through a dense busbar bridge, which is connected to the local distribution box Panelboard.
Recently Posted
-
Copper Bar Design - Summary Chapter
May 15, 2026The design of copper bars in switchgear is a systematic project, and it cannot be simply said that the selection of copper bars ba
Read More -
Structural Design of Medium Voltage Switchgear
May 14, 2026Structural Design of Medium Voltage SwitchgearBasic requirements, should know and be able to:Insulation distance, including electr
Read More -
Why do some "ring main unit gas boxes" have observation windows while others do not? What is their f
May 14, 2026The observation window on the gas box of the ring main unit is a common design, mainly used to facilitate operators to observe the
Read More -
Basic knowledge of secondary grounding for current transformers and voltage transformers
April 24, 20261、 The 'fatal' hazard of current transformers: open circuit on the secondary sideIn the vast context of the power system,
Read More